How Many A3L Chillers Can I Have In One Room?
At Applied Thermal Control, we understand that the use of A3L refrigerants such as R290 naturally raises questions around safety, compliance, and room limits. This article is designed to reassure users of modern A3L refrigerant chillers and explain how room size, refrigerant charge, and applicable standards work together.
Why Safety Standards Consider Room Size for A3L Refrigerants:
R290 is classified as an A3L refrigerant due to its high flammability. As a result, safety standards are designed to ensure that, in the unlikely event of a complete refrigerant release, the concentration of gas in the occupied space remains below a defined fraction of the Lower Flammability Limit (LFL).
In Europe and the UK, this principle is defined within EN 378 and IEC 60335-2-89, while in the United States the same objective is set out in ASHRAE Standard 15 and UL 60335-2-89. Although the documents differ in structure, all of these standards assess safety based on worst-case leak scenarios rather than normal operating conditions.
Independent Circuits and Refrigerant Charge
Modern laboratory and process chillers using R290 are designed with very small refrigerant charges, typically well below 150g per circuit. Each chiller operates as a hermetically sealed, independent refrigeration system, meaning that compliance is assessed per individual circuit rather than simply summing the total refrigerant charge across all equipment in a room.
This approach is fundamental to EN 378, IEC 60335-2-89, ASHRAE 15, and UL 60335-2-89, and is why multiple low-charge A3L systems are widely accepted in laboratory and industrial environments across Europe, the UK, and the US.
The Significance of the 150g Threshold
Historically, refrigerant charges below 150g per circuit have been treated as low-risk category across global safety standards. Under EN 378 and IEC 60335-2-89 (and their US adoptions), systems below this threshold do not normally require permanently installed, automatic leak detection.
Instead, safety is achieved by design. The manufacturer must demonstrate that a full refrigerant release from a single circuit cannot result in a concentration exceeding a defined fraction of the LFL near potential ignition sources. In Europe and the UK, this is typically set at 50% of the LFL, while in the US standards such as ASHRAE 15 apply similarly conservative limits, often expressed as 25% of the LFL where mitigation systems are involved.
Worked Example: How Many G02 (2.15kW Cooling Capacity) Chillers Can Be Installed in a 20m2 Room?
To illustrate how current safety standards apply in practice, consider a 20 square metre laboratory or technical room fitted with ATC G02 2.15kW recirculating chillers, each containing 95g of R290 (propane).
Each ATC G02 is a hermetically sealed, self-contained refrigeration system with an independent refrigerant circuit. With a refrigerant charge well below the widely recognised 150g per-circuit threshold, each unit falls into the low-charge category addressed by EN 378, IEC 60335-2-89, ASHRAE Standard 15, and UL 60335-2-89.
Under these standards, safety is assessed on the basis of a single worst-case-leak from one circuit, not the combined refrigerant charge of all equipment in the room. In a 20m2 space, the full release of 95g of R290 from one G02 would not result in a refrigerant concentration exceeding the allowable fraction of the Lower Flammability Limit, provided the room has normal laboratory or plant-room ventilation.
Because each G02 is independently compliant, multiple units may be installed in the same room without triggering additional safety measures such as permanent leak detection or forced ventilation. In practical terms, a 20m2 room can typically accommodate five or more G02 chillers, assuming that:
– Each unit remains below 150g or refrigerant
– The room is not fully sealed
– The space is classified as non-public (e.g. laboratory or technical area)
Even as the number of units increases, compliance is maintained because no single refrigerant circuit can release enough gas to exceed concentration limits defined by international safety standards.
This design-based approach is the reason that low-charge A3 refrigerant chillers such as the G02 are widely used in laboratories and industrial environments worldwide.
Ventilation Considerations
Ventilation is treated as a supporting safety measure in all major standards. Propane is heavier than air, so adequate air movement helps to prevent gas accumulation near floor level in the event of a leak. Most laboratory and technical spaces already provide sufficient ventilation for low-charge systems, and additional measures are generally only required in very small or fully enclosed rooms.
Public and Non-Public Occupancy
Safety standards distinguish between public and non-public spaces. Laboratories, plant rooms, and technical areas are typically classified as non-public and allow greater flexibility than publicly accessible areas. Most Applied Thermal Control installations fall into this non-public category under both European and US frameworks.
International safety standards take a consistent, risk-based approach to A3 refrigerants. For modern, low-charge systems, most common installations are well within recognised limits when assessed in accordance with EN 378, IEC 60335-2-89, ASHRAE Standard 15, and UL 60335-2-89.
If you require confirmation for a specific room layout or application, our team can provide guidance as part of the project planning process.
Important Note on Application-Specific Assessments
The information provided in this article is intended as general guidance based on typical laboratory and technical room conditions and the application of recognised safety standards. Final suitability for any installation will depends on site-specific factors such as room geometry, ceiling height, ventilation rate, occupancy classification, local regulatory requirements, and the exact equipment configuration. While modern low-charge A3 refrigerant chillers are designed to operate safely without active leak detection, individual projects may require a formal risk assessment or approval by a responsible safety officer, facilities team, or local authority.
We recommend that all installations are reviewed in line with applicable national and local regulations and that equipment is installed, operated, and maintained in accordance with manufacturer instructions and recognised good engineering practices.