Cooling capacity
(setpoint 20°C, ambient 20°C) | | K4/4500W | | K6/6000W | | K9/9000W | | K12/14000W |
Physical attributes | | | | | | | | |
Physical dimensions (LxWxH) (mm) | | L775 x W510 x H850mm | | L775 x W510 x H850mm | | L775 x W510 x H850mm | | L775 x W510 x H1130mm |
Weight (kg) | | 125 | | 125 | | 125 | | 135 |
Noise level (dB(A)) | | 68 | | 68 | | 85 | | 85 |
Toolless access | | Yes | | Yes | | Yes | | Yes |
| | | | | | | | |
Temperature control attributes | | | | | | | | |
Technology | | Vapour Compression | | Vapour Compression | | Vapour Compression | | Vapour Compression |
Temperature range (standard) | | +4°C to +35°C | | +4°C to +35°C | | +4°C to +35°C | | +4°C to +35°C |
Control method | | PID | | PID | | PID | | PID |
Temperature stability (with constant load) | | ±0.1°C | | ±0.1°C | | ±0.1°C | | ±0.2°C |
Temperature resolution | | 0.1°C | | 0.1°C | | 0.1°C | | 0.1°C |
| | | | | | | | |
Water circuit attributes | | | | | | | | |
System volume (L) | | 5 | | 5 | | 5.25 | | 5.5 |
Pump options | | P5, P10, P17, P25 | | P5, P10, P17, P25 | | P5, P10, P17, P25 | | P5, P10, P17, P25 |
Pressure control (settable pressure relief valve) | | Internal, PRV, 20-150psi*not on centrifugal pump | | Internal, PRV, 20-150psi*not on centrifugal pump | | Internal, PRV, 20-150psi*not on centrifugal pump | | Internal, PRV, 20-150psi*not on centrifugal pump |
Standard fittings | | 1/2" BSPPF | | 1/2" BSPPF | | 1/2" BSPPF | | 1/2" BSPPF |
| | 3/8" + 1/2" hose barbs | | 3/8" + 1/2" hose barbs | | 3/8" + 1/2" hose barbs | | 3/8" + 1/2" hose barbs |
Standard chemical compatibility | | Hexid Fluid, DI Water, Propylene Glycol | | Hexid Fluid, DI Water, Propylene Glycol | | Hexid Fluid, DI Water, Propylene Glycol | | Hexid Fluid, DI Water, Propylene Glycol |
| | | | | | | | |
Electrical attributes | | | | | | | | |
(90-264Vac, 1/2, 50-60Hz) U-spec | | - | | - | | - | | - |
(230Vac, 1, 50Hz) 0-spec | | Available, 13A | | Available, 13A | | Available, 20A | | - |
(115Vac, 1, 60Hz) 1-spec | | - | | - | | - | | - |
(208-220Vac, 1/2, 60Hz) 2-spec | | Available, 11.9A | | Available, 11.A | | - | | - |
(400Vac, 3, 50Hz) 3-spec | | - | | Available, 5A | | Available, 10A | | Available, 13A |
(460Vac, 3, 60Hz) 4-spec | | - | | - | | - | | - |
5-spec | | - | | - | | - | | - |
(Switchable 208Vac, 1/2, 60Hz | 220Vac, 1/2, 60Hz | 230Vac, 1, 50Hz) 6-spec | | Available, see rows -0, -2, -3spec | | Available, see rows -0, -2, -3spec | | - | | - |
(Switchable 115Vac, 1, 60Hz | 220Vac, 1/2, 60Hz | 230Vac, 1, 50Hz) 7-spec | | - | | - | | - | | - |
(208Vac, 3, 60Hz) 8-spec | | - | | Available, 7.5A | | Available, 17.5A | | Available, 23A |
(208-230Vac, 1/2, 50/60Hz) 9-spec | | - | | - | | - | | - |
| | | | | | | | |
Safety and fault indicator | | | | | | | | |
1st party approvals | | CE | | CE | | CE | | CE |
3rd party approvals | | UL-OK on 9, 8 or 3-spec | | UL-OK on 9, 8 or 3-spec | | UL-OK on 9, 8 or 3-spec | | UL-OK on 9, 8 or 3-spec |
Empty fluid reservoir alarm | | Safety interlock | | Safety interlock | | Safety interlock | | Safety interlock |
Low fluid flow alarm | | N/A | | N/A | | N/A | | N/A |
Temperature out of range alarm | | N/A | | N/A | | N/A | | N/A |
Compressor HP switch | | Standard | | Standard | | Standard | | Standard |
Motor thermal overload | | Standard | | Standard | | Standard | | Standard |
Emergency off | | Not present | | Not present | | Not present | | Not present |
Warranty options | | 2 year parts, 1 year labour | | 2 year parts, 1 year labour | | 2 year parts, 1 year labour | | 2 year parts, 1 year labour |
| | Enhanced warranty options | | Enhanced warranty options | | Enhanced warranty options | | Enhanced warranty options |
Overcurrent fault-cleared restart mode | | Manual | | Manual | | Manual | | Manual |
Overcurrent protection | | Standard, via GV2 breaker | | Standard, via GV2 breaker | | Standard, via GV2 breaker | | Standard, via GV2 breaker |
Interlock restored, restart mode | | Manual by default | | Manual by default | | Manual by default | | Manual by default |
| | Specify automatic with 'A' suffix on model number | | Specify automatic with 'A' suffix on model number | | Specify automatic with 'A' suffix on model number | | Specify automatic with 'A' suffix on model number |
| | | | | | | | |
Options available | | | | | | | | |
Remote alarm/power-off; SA00001 | | Available only with auto-restart | | Available only with auto-restart | | Available only with auto-restart | | Available only with auto-restart |
Low temperature pack; SA00002 | | Available, to -20°C | | Available, to -20°C | | Available, to -20°C | | Available, to -20°C |
High temperature pack; SA00003 | | Available, to +80°C | | Available, to +80°C | | Available, to +80°C | | Available, to +80°C |
Water cooled KT; SA00004 | | - | | - | | - | | - |
Water cooled K1; SA00005 | | - | | - | | - | | - |
Water cooled K4/K6/K9/K12; SA00006 | | Available | | Available | | Available | | Available |
Water cooled K3; SA00007 | | - | | - | | - | | - |
Non-return solenoid pack; SA00008 | | Available | | Available | | Available | | Available |
High temperature water circuit w/o heater; SA00009 | | - | | - | | - | | - |
Low flow alarm (KT); SA00010 | | Available | | Available | | Available | | Available |
Onboard RS485 data protocol; SA00011 | | Available | | Available | | Available | | Available |
Standard VFC set; SA00012 | | Available | | Available | | Available | | Available |
In-line Deionising cartridge and fittings; SA00013 | | Available | | Available | | Available | | Available |
Stainless non-return solenoid valve; SA00014 | | - | | - | | - | | - |
Castors to replace rubber feet; SA00015 | | - | | - | | - | | - |
CPC quick release connectors; SA00016 | | Available, up to 20L/min | | Available, up to 20L/min | | Available, up to 20L/min | | Available, up to 20L/min |
Installation kit; SA00017 | | Available | | Available | | Available | | Available |
Stainless steel pump and fittings; SA00018 | | - | | - | | - | | - |
KT filter kit; SA00019 | | - | | - | | - | | - |
Mod for outdoor use; SA00020 | |
Available,
to IP54 | |
Available,
to IP54 | |
Available,
to IP54 | |
Available,
to IP54 |
Particulate filter; SA00021 | | Available | | Available | | Available | | Available |
Flow meter pack; SA00022 | | Available | | Available | | Available | | Available |
Fan speed control (on/off); SA00023 | | - | | - | | - | | - |
Fan speed control (proportional); SA00024 | | - | | - | | - | | - |
Flow meter pack output to RS485; SA00025 | | Available | | Available | | Available | | Available |
Seismic mounts; SA00026 | | Available | | Available | | Available | | Available |
In-line UV decontamination; SA00027 | | Available | | Available | | Available | | Available |
Qwikfoot kit; SA00028 | | Available | | Available | | Available | | Available |
Stainless enclosure; SA00029 | | Available | | Available | | Available | | Available |
De-branding of standard model; SA00030 | | Available | | Available | | Available | | Available |
High ambient fans; SA00031 | | Available | | Available | | - | | - |
Frost protection; SA00041 | | - | | - | | - | | - |
External manifold (2-way); SA00042 | | Available | | Available | | Available | | Available |
External manifold (10-way); SA00050 | | Available | | Available | | Available | | Available |
Remote stop-start; SA00051 | | Available | | Available | | Available | | Available |
| | | | | | | | |